Gas Discharge Tube (GDT) Selection Pitfall Avoidance Guide

"I need to protect my RS485, Ethernet, or telecom lines from lightning surge damage. I've heard that gas discharge tubes (GDTs) are good, but if GDTs are so good, why can't they be used directly on 220V AC power lines as primary protection? What is the real difference between a GDT and a varistor (MOV)?"

This is an excellent entry point, as it touches upon the core logic of surge protection technology. To help engineers and procurement decision-makers clarify these concepts and avoid selection errors, Shanghai Leiditech, based on industry standards such as the IEC 61643 series, provides a detailed breakdown of the true role of gas discharge tubes (GDTs), their working principles, and the best practices for their use in modern electronic protection.

I.The Secret of GDT: Precision Structure and "Switch" Mechanism

 

1. Quick Overview: What is a Gas Discharge Tube?

A gas discharge tube (GDT) is a hermetically sealed ceramic device filled with an inert gas and containing two or three metal electrodes. Under normal operating conditions, it is electrically "invisible" (insulation resistance ≥ 1 GΩ). When a surge exceeding its breakdown voltage appears, it switches to a near-short-circuit state within nanoseconds — diverting the surge current to ground — and then extinguishes itself.

 

Due to their capacitance of less than 2pF and high surge current handling capability, GDTs are the standard first-stage protection component in surge protective devices (SPDs) for signal lines such as RS485, Ethernet, and telecommunications. The internal electrode surfaces of GDTs are typically coated with a special emissive material to reduce electron emission energy and stabilize the arc. Among materials, ceramic is the mainstream choice for Leiditech's GDT products due to its excellent thermal expansion coefficient matching and extremely high heat resistance, enabling stable structural performance under extreme environments.

Two standard configurations:

Two-electrode GDT:Single gap, 1-mode protection (line-to-ground or line-to-line). This is the standard configuration for single-mode signal line protection.

Three-electrode GDT: Two gaps share a common central electrode. It simultaneously protects both conductors of a balanced differential pair — essential for RS485, twisted-pair, and telecom circuits.

 

 Above: 2R for two-electrode, 3R for three-electrode.

Hermetic sealing is critical. Seal failure allows atmospheric air to enter, destroying the defined breakdown characteristics. The quality of a GDT depends heavily on the sealing process — which is why it is essential to specify products from a reputable manufacturer like Shanghai Leiditech.

2.Core Mechanism: Switch, Not Clamp — The Difference from MOV

 

GDT (Gas Discharge Tube): Acts like a high-voltage switch. Under normal operating voltage, it presents extremely high impedance (≥1GΩ), remaining nearly transparent to the circuit; once the transient voltage exceeds its breakdown threshold, the electric field instantly ionizes the gas, forming a conductive plasma channel within nanoseconds, transitioning from an open state to a near short-circuit state, shunting surge current to ground. This differs from a varistor (MOV), which gradually clamps voltage.

Key differences between GDT and MOV:

 

Parameters

Gas Discharge Tube (GDT)

Varistor (MOV)

Working mechanism

Switching type — sharp transition from open circuit to short circuit

Clamping type — impedance gradually decreases

Normal-state impedance

≥ 1 GΩ — zero leakage current

Higher but finite — with small leakage current; increases with age

Voltage after triggering

~15–30 V arc voltage

Depends on type and current, up to 1.5–4.0 kV

Surge current capacity

For signal lines: GDT is 5–20 kA (8/20 µs)

Large industrial MOVs up to 40–100 kA (8/20 μs)

Capacitance

< 2 pF — suitable for high-frequency signal lines

100–5,000 pF — limits their use on high-speed signal lines

Follow-on current risk

High risk on power lines — requires coordination with MOV

Self-extinguishing — no follow-on current issue

Degradation

Gas consumption after multiple operations

ZnO grain degradation; clamping voltage drifts after repeated surges

Primary SPD role

Signal line SPD (IEC 61643-21) — RS485, Ethernet, coaxial cable, telecommunications

Type 2 AC power SPD (IEC 61643-11) — distribution board clamping

3. The Four Stages of GDT Operation

l Off-state: Circuit operates normally; GDT is "invisible" with extremely high insulation resistance.

l Pulse ignition (glow region): Surge voltage reaches the threshold, and the gas begins to ionize.

l Arc (conduction): A low-impedance path is instantly formed. At this point, the tube voltage drop is extremely low (only about 10-30V), allowing surge currents of up to tens of kiloamperes to be discharged, regardless of whether the incoming surge is several thousand or tens of thousands of volts.

l Extinction and recovery: After the surge energy is dissipated, when the current drops below the minimum required to sustain the arc, the GDT automatically extinguishes and returns to its high-impedance state, ready for the next transient.

 

 

II.Environmental Adaptability: Unaffected by Extreme High and Low Temperatures

 

In industrial and outdoor applications, the impact of ambient temperature on protection devices cannot be ignored. Thanks to the precision design of the ceramic housing and internal gas pressure, Leiditech GDTs demonstrate excellent temperature adaptability.

Generally, the rated operating temperature range of GDTs is between -40°C and +85°C. However, for harsh industrial or outdoor scenarios, Leiditech offers wide-temperature models with operating temperatures up to -40°C to +125°C. Even under extreme cold of -55°C or high temperatures of 125°C, the breakdown voltage variation of GDTs remains minimal. This extremely high stability makes them perform exceptionally well in scenarios with drastic temperature fluctuations, such as base station communications and outdoor security.

III.GDT follow-on current issue

 

Many customers assume that since GDTs can handle high currents, they are certainly suitable for use at the power entry point. This is a dangerous misconception.

Where does the problem lie? — "Power-frequency follow-on current"

Phenomenon: After a GDT operates on a 220V/380V AC circuit, even though the lightning surge has passed, the power frequency voltage (220V) of the grid still exists.

Consequence: Since the holding voltage of a GDT after conduction is only about 20V, far lower than the grid's 220V, the grid current will continuously flow through the GDT to ground (i.e., "power-frequency follow-on current"). The GDT cannot cut off this current on its own, which can cause the GDT to overheat and explode, or even start a fire.

l Shanghai Leiditech's solution:

MOV and GDT coordinated use: When a surge arrives, the GDT and MOV conduct sequentially, providing surge protection. After the lightning strike passes, the MOV turns off normally, the GDT arc extinguishes, and the circuit returns to normal operation with no arc continuation. The schematic diagram is as follows:

 

IV.The True Domain of GDT: Signal and Data Line Protection

 

The true value of GDT lies in the protection of signal lines (RS485, Ethernet, coaxial cable, telephone lines). This is the core strength of Shanghai Leiditech's product portfolio.

Why are signal lines exclusively suited for GDT? — Ultra-low capacitance

1. Technical conflict: Signal lines transmit high-frequency data. Any capacitance in parallel with the signal line will attenuate the signal and cause waveform distortion.

2. GDT advantage: GDTs have extremely low parasitic capacitance (typically < 2 pF).

3. Comparison: MOV capacitance typically ranges from 100pF to several thousand pF. If an MOV is used on a Gigabit Ethernet or high-definition video line, the signal would be "eaten up" by the capacitance before it can even be transmitted. In contrast, a GDT's < 2pF capacitance has almost no effect on the signal.

Therefore, in signal surge protective devices compliant with IEC 61643-21, GDT is the preferred first-stage protection component.

V.Shanghai Leiditech Recommended: Key GDT Selection Parameters

 

The table below shows the parameters of Leiditech product 3R090MFH-5S; the parameter introduction is based on this product.

 

 

Parameter name

Description

Selection Recommendations

DC Breakdown Voltage (Vdc)

DC spark-over voltage

Must be higher than the maximum normal operating voltage of the circuit (e.g., 90V or 120V is typically selected for RS485 Vdc).

Impulse Spark-over Voltage (Vimp)

Impulse spark-over voltage

Determines the response speed when lightning strikes; must be lower than the device's withstand voltage.

Arc Voltage (Varc)

Arc voltage

Typically 15-30V. This is the residual voltage after GDT conduction, which is very low and extremely friendly to downstream equipment.

Capacitance

Parasitic capacitance

< 2 pF is the key to ensuring high-frequency signal integrity.

Surge Current (8/20 µs)

Surge current capability

Select according to the installation environment (e.g., 5kA, 10kA, 20kA).

Number of Electrodes

Number of electrodes

2-electrode: single-line protection; 3-electrode: used for differential signals (e.g., RS485), ensuring both lines operate simultaneously for more balanced protection.

VI.GDT Selection Examples

AC220V, power line 2kV line-to-line, 4kV line-to-ground protection level, circuit design as follows:

1) AC220V is greater than the arc voltage (10V), so a GDT cannot be used directly for protection.

2) DC breakdown voltage must meet: min(Udc) ≥ 1.8 × 1.414 × 220 = 560V. Choose a value close to this; Udc = 600V.

3) Withstand voltage should be determined based on the downstream components.

4) Line-to-line 2kV, internal resistance per standard is 2Ω, so 2000 ÷ 2 = 1000A. Therefore, the GDT's surge current capability must be at least 1kA.

5) Package: Through-hole or SMD?

 

VII.GDT Application Circuits

 

1. AC110V/AC220V AC surge protection solution

 

2. DC48V Surge Protection Solution

 

3.Ethernet Port Surge Protection Solution

 

4. RF/WiFi Antenna Surge Protection Solution

 

If you have any requirements for the above solutions, please feel free to contact Shanghai Leiditech sales representatives or the EMC engineer.

VIII.Leiditech GDT dimensions

Part No.

Package

Size

Impulse Discharge Current 
(8/20 µs)10times(KA)

SMB075-SMB600

SMD

3.2*1.6*1.6

0.5

SMD3225-(090-800)NF

SMD

3.2*2.5*2.5

1

SMD3225-090NFH.

SMD

3.2*2.5*2.5

2

SMD4532-(070-1500)NF

SMD

4.5*3.2*2.7

2

2R(075-1200)-4S

SMD

4.2*4.2*4

5

SMD5542-(800-3600)

SMD

4.2*4.2*5

3

SMD5050-(075-1200)

SMD

5*5*4.2

5

2R(075-3600)-5L/S

DIP/SMD

5.5*6

5

2R(075-800)SA-6

SMD

6.2*6.2*4.2

5

2R(075-600)(T.S)B-5

DIP/SMD

6*5.5

5

2R(075-800)(T.S)B-8

DIP/SMD

8*6

10

2R(075-800)(T.S)D-8

DIP/SMD

8*6

20

 